Certification: | VDE, CCC, ISO9001 |
---|---|
Shell Material: | Aluminum-Zinc Coated Steel Sheet |
Voltage Level: | High Voltage |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
S.N. | Name | Unit | Date |
1 | rated voltage | kV | 40.5 |
2 | rated current | A | 1250 1600 2000 |
3 | rated frequency | Hz | 50 |
4 | rated short time withstand current | kA | 20 25 31.5 |
5 | rated peak withstand voltage | kA | 50 63 80 |
6 | rated power frequency withstand voltage | kV | 95/1 min |
7 | rated lighting impluse withstand voltage | kV | 185 |
8 | rated duration of short circuit | s | 4 |
9 | the degree of protection | IP3X |
S.N. | Name | Unit | Date |
1 | rated voltage | kV | 40.5 |
2 | rated frequency | Hz | 50 |
3 | rated power frequency withstand voltage | kV | 95/1 min |
4 | rated lighting impluse withstand voltage | kV | 185 |
5 | rated current | A | 1250 1600 2000 |
6 | rated short time withstand current | kA | 20 25 31.5 |
7 | rated short circuit withstand current | kA | 20 25 31.5 |
8 | rated peak withstand voltage | kA | 50 63 80 |
9 | rated duration of short circuit | s | 4 |
10 | opening time | s | 30≤t≤60 |
11 | closing time | s | 50≤t≤100 |
12 | breaking times of the rated short circuit breaking current | cycles | 20 |
13 | mechanical endurance | cycles | 10000 |
Name | Unit | Data | |
rated operate voltage | opening coil | V | DC220/110 AC220/110 |
closing coil | |||
rated operate current | opening coil | A | 0.96(220V) 1.05(110V) |
closing coil | |||
power of energy-stored motor | W | 230 | |
rated voltage of energy-stored motor | V | DC220/110 AC220/110 | |
distribution for storing energy | s | ≤12 |