Breaking Capacity: | High Voltage Circuit Breakers |
---|---|
Operation: | Electric Type |
Speed: | High-Speed Circuit Breaker |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
S.N | Name | Unit | Data |
1 | Rated voltage | kV | 12 |
2 | Rated frequency | Hz | 50/60 |
3 | Rated current | A | 630/1250/1600/2000/2500/3150 |
4 | Rated short circuit breaking current | kA | 25/31.5/40 |
5 | Rated peak withstand current | kA | 63/80/100 |
6 | Rated short-circuit duration | s | 4 |
7 | Electrical endurance class | Cycle | 30/20 |
8 | Mechanical endurance | Cycle | 10000 |