Breaking Capacity: | High Voltage Circuit Breakers |
---|---|
Operation: | Electric Type |
Speed: | High-Speed Circuit Breaker |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
S.N | Name | Unit | Data | |
1 | Rated voltage | kV | 12 | |
2 | Rated power frequency withstand voltage 1min | kV | 42 | |
3 | Rated lightning impulse withstand voltage | kV | 75 | |
4 | Rated frequency | Hz | 50 | |
5 | Rated current | A | 630 | 1250 |
6 | Rated short circuit breaking current | kA | 20 | 20 |
25 | 25 | |||
31.5 | 31.5 | |||
7 | Rated peak withstand current | kA | 50 | 50 |
63 | 63 | |||
80 | 80 | |||
8 | Conductive circuit resistance of each phase | μΩ | <=50 | <=45 |
S.N | Name | Unit | Data |
1 | Clearance between open contacts | mm | 9±1 |
2 | Over travel of contacts | mm | 3.5±0.5 |
3 | Contact bouncing duration at closing opening | ms | ≤2 |
4 | Out of Simultaneity of CO operation of three poles | ms | ≤2 |
5 | Opening time | ms | 20~50 |
6 | Closing time | ms | 30~70 |
7 | Average opening speed | m/s | 0.9~1.3 |
8 | Average closing speed | m/s | 0.4~0.8 |