Breaking Capacity: | High Voltage Circuit Breakers |
---|---|
Operation: | Electric Type |
Speed: | High-Speed Circuit Breaker |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Item | Name | Unit | Value | |
1 | Clearance between open contacts | mm | 9±1 | |
2 | Overtravel | 3.5±0.5 | ||
3 | Center distance between phase |
210±1 | ||
4 | Contact closing jump time | MS | ≤3 | |
5 | open Close/ asynchronized of three phases | ≤2 | ||
6 | Opening time | 20~50 | ||
7 | Closing time | 30~70 | ||
8 | 6mm Average opening speed After contact separate 6mm |
M/S | 1.1±0.2 | |
9 | Average closing speed the whole process |
0.6±0.2 | ||
10 | After Closing , contact pressure |
N | 25KA | 31.5KA |
2900±200 | 3 100±200 |