| Breaking Capacity: | High Voltage Circuit Breakers |
|---|---|
| Operation: | Electric Type |
| Speed: | High-Speed Circuit Breaker |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
| S.N | Name | Unit | Data | ||||
| 1 | Rated voltage | kV | 12 | ||||
| 2 | Rated frequency | Hz | 50/60 | ||||
| 3 | Rated current | A | 630 | 630 | 1250 | 1600 | |
| 1000 | 1000 | 1600 | 2000 | ||||
| 1250 | 1250 | 2000 | 2500 | ||||
| 3150 | |||||||
| 4 | Rated short circuit breaking current | kA | 20 | 25 | 31.5 | 40 | |
| 5 | Rated peak withstand current | kA | 50 | 63 | 80 | 100 | |
| 6 | Rated short-circuit duration | S | 4 | ||||
| 7 | Rated power frequency withstand voltage |
Between phases, phase to ground |
kV | 42 | |||
| Between gaps | kV | 48 | |||||
| 8 | Rated lightning impulse withstand voltage |
Between phases, phase to ground |
kV | 75 | |||
| Between gaps | kV | 85 | |||||
| 9 | Rated operating sequence | O-0.3S-CO-180S-CO
O-180S-CO-18S-CO
(above 40kA) |
|||||
| 10 | Rated breaking current of single capacitor bank | A | 630 | ||||
| 11 | Rated breaking current of bank to bank capacitor bank | A | 400 | ||||
| 12 | Electrical endurance class | Cycle | 30 | ||||
| 13 | Mechanical endurance | Cycle | 10000 | ||||
| 14 | Clearance between open contacts | mm | 11±1 | ||||
| 15 | Contact stroke of contacts | mm | 4±1 | ||||
| 16 | Out of simultaneity of CO operation of three poles | ms | ≤2 | ||||
| 17 | Contact bouncing duration at closing operation | ms | ≤2 | ||||
| 18 | Closing time | ms | 50~100 | ||||
| 19 | Opening time | ms | 20~60 | ||||
| 20 | Average closing speed | m/s | 0.6±0.2 | ||||
| 21 | Average opening speed | m/s | 1.1±0.2 | ||||
| 22 | Main circuit resistance of each pole | μΩ | ≤40 | ≤30 | |||
| 23 | DC component | 50%(Max.) | |||||