Breaking Capacity: | High Voltage Circuit Breakers |
---|---|
Operation: | Electric Type |
Speed: | Normal Type Circuit Breaker |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
NO. | Name | Unit | Dada | ||
1 | rated voltage | kV | 40.5 | ||
2 | rated current | A | 1250 1600 2000 | ||
3 | rated frequency | Hz | 50 | ||
4 | rated short-circuit breaking current | kA | 20 25 31.5 | ||
5 | rated short-circuit closing current | kA | 50 63 80 | ||
6 | rated peak withstand current | kA | 50 63 80 | ||
7 | rated short-time withstand current | kA | 20 25 31.5 | ||
8 | rated short-circuit duration | s | 4 | ||
9 | rated operation sequence | 0-0.3s-CO-180s-CO | |||
10 | short-circuit breaking current in remote ground fault condition | kA | 17.54 21.93 27.6 | ||
11 | rated insulation leval |
1 min power frequency withstand voltage(peak value) | dry test | kV | 95 |
wet test | kV | 85 | |||
rated lighting impluse withstand voltage | kV | 185 | |||
12 | opening time | ms | <=100 | ||
13 | mechanical endurance | cycles | 10000 | ||
14 | breaking operations of rated short circuit breaking current | cycles | 20 |
No. | Name | Unit | Data | |
1 | clearance between open contacts | mm | 20±2(central type) | |
22±2(lateral type) | ||||
2 | over travel of contacts | mm | 4±1 | |
3 | allowed wear thickness of contacts | mm | 3 | |
4 | average closing speed | m/s | 0.6±0.2 | |
5 | average opening speed (befiore contact oil buffer) | m/s | 1.6±0.2 | |
6 | contact bouncing duration at closing operation | ms | <=3(31.5kA) <=3(20~25kA) | |
7 | synchronism of closing contact | ms | <=2 | |
8 | un-synchronism of opening contact | ms | <=2 | |
9 | bouncing amplitude of opening contact | mm | <=3 | |
10 | closing time | ms | 50<=t<=120 | |
11 | opening time | max and rated voltage | ms | 20<=t<=60 |
min rated voltage | ms | 20<=t<=60 | ||
12 | closing-opening time | ms | <=100 | |
13 | contact pressure | N | 3100±200 | |
14 | main circuit resistance | μΩ | <=50(without transformer) |