• 40.5 Kv HV Vacuum Switchgear/36 KV Switchgear
  • 40.5 Kv HV Vacuum Switchgear/36 KV Switchgear
  • 40.5 Kv HV Vacuum Switchgear/36 KV Switchgear
  • 40.5 Kv HV Vacuum Switchgear/36 KV Switchgear
  • 40.5 Kv HV Vacuum Switchgear/36 KV Switchgear
  • 40.5 Kv HV Vacuum Switchgear/36 KV Switchgear

40.5 Kv HV Vacuum Switchgear/36 KV Switchgear

Certification: VDE, CCC, ISO9001
Shell Material: Aluminum-Zinc Coated Steel Sheet
Voltage Level: High Voltage
Installation: Indoor Fixed
Structure: Cabinet
Current: AC
Manufacturer/Factory & Trading Company
Diamond Member Since 2008

Suppliers with verified business licenses

Shaanxi, China
Importers and Exporters
The supplier has import and export rights
High Repeat Buyers Choice
More than 50% of buyers repeatedly choose the supplier
Years of Export Experience
The export experience of the supplier is more than 10 years
Fast Delivery
The supplier can deliver the goods within 15 days
to see all verified strength labels (28)

Basic Info.

Model NO.
KYN61-40.5(Z)
Transport Package
Non-Solid Wooden Case
Trademark
Longxiang
Origin
Baoji, Shaanxi China
Production Capacity
10000sets/Year

Product Description

KYN61-40.5(Z) indoor high voltage vacuum switchgear


Main characteristicss
The switchgear is assembly type.The circuit breaker is floor roll-out. Adopted new compound insulation vacuum circuit breaker has the features of good interchange ability and easy replacement.

The truck shelf is equipped with lead-screw drive mechanism, which can move truck easily and prevent the mechanism be damaged from faulty operation.

All the operations can be done with the door shut. All interlocks connecting with the main switch, truck and door of switchgear adopt compulsive mechanical lock and can meet the requirements of "FIVE PREVENTION".

The space of the cable comparment is abundant for the connection of several cables.
The instant earthing switch is used for earthing and short-circuiting of the circuit .
The degree of protection for the enclosure is IP3X.It is IP2X when the door of truck comparment open.
It conforms to GB3906-2006, DL404-2007 and refers to IEC-298 standard.



General description
KYN61-40.5(Z) type indoor HV vacuum switchgear(hereinafter called switchgear) is three-phase AC 50Hz indoor power distribution equipment with the rated range voltage of 40.5kV. It is used for power reception and distribution of the power station,substation mining and industrial enterprise for the control, protection and monitor of the circuits, It can be used in the fields where it is operated frequently.


Applying ambient conditions
Ambient temperature:The max temperature should be +40ºC.The average value in 24 hours should be no more than 35ºC,the min temperature should be -10ºC.
The height above sealevel should be no higher than 1000m.
Relative humidity:daily average relative humidity≤95%,monthly average relative humidity≤90%
Earthquake intensity:not exceed 8 degrees
Saturated vapour pressure:daily average value2.2kPa, monthly average value≤1.8kPa
It should be used in the place where it is free from fire, explosion, serious filth, chemical erosion and violent vibration.



Main technical data of the vacuum switchgear
S.N. Name Unit Date
1 rated voltage kV 40.5
2 rated current A 1250 1600 2000
3 rated frequency Hz 50
4 rated short time withstand current kA 20 25 31.5
5 rated peak withstand voltage kA 50 63 80
6 rated power frequency withstand voltage kV 95/1 min
7 rated lighting impluse withstand voltage kV 185
8 rated duration of short circuit  s 4
9 the degree of protection   IP3X


Main technical data of the vacuum circuit breaker
S.N. Name Unit Date
1 rated voltage kV 40.5
2 rated frequency Hz 50
3 rated power frequency withstand voltage kV 95/1 min
4 rated lighting impluse withstand voltage kV 185
5 rated current A 1250 1600 2000
6 rated short time withstand current kA 20 25 31.5
7 rated short circuit withstand current kA 20 25 31.5
8 rated peak withstand voltage kA 50 63 80
9 rated duration of short circuit  s 4
10 opening time s 30≤t≤60
11 closing time s 50≤t≤100
12 breaking times of the rated short circuit breaking current  cycles 20
13 mechanical endurance cycles 10000


Main technical data of spring operating mechanism
Name  Unit Data
rated operate voltage opening coil V DC220/110 AC220/110
closing coil
rated operate current opening coil A 0.96(220V) 1.05(110V)
closing coil
power of energy-stored motor W 230
rated voltage of energy-stored motor V DC220/110   AC220/110
distribution for storing energy s ≤12


The overall dimension of the switchgear 
Over dimension(width*depth*height):1400*2800*2600mm


The construction drawing of the switchgear 
A.Relay instrument component
B.Bus-bar component
C.Circuit breaker component
D.Cable component


40.5 Kv HV Vacuum Switchgear/36 KV Switchgear
Installation of the switchgear
The distance between the back of the switchgear to the wall:≥1500mm
The evenness of the basic framework:≤1mm/square meter
The height of embedded steel channel above the groud should not exceeded 3mm
The weight of the switchgear is about 1800kg
The width of the operating corridot of the switchgear (single line):≥3000mm,double lines(face to face)≥4000mm.

40.5 Kv HV Vacuum Switchgear/36 KV Switchgear
Mounting fundation drawing 
40.5 Kv HV Vacuum Switchgear/36 KV Switchgear
Our Factory

40.5 Kv HV Vacuum Switchgear/36 KV Switchgear
40.5 Kv HV Vacuum Switchgear/36 KV Switchgear
40.5 Kv HV Vacuum Switchgear/36 KV Switchgear
40.5 Kv HV Vacuum Switchgear/36 KV Switchgear
40.5 Kv HV Vacuum Switchgear/36 KV Switchgear


Our Certificates

40.5 Kv HV Vacuum Switchgear/36 KV Switchgear
40.5 Kv HV Vacuum Switchgear/36 KV Switchgear
40.5 Kv HV Vacuum Switchgear/36 KV Switchgear
Welcome for enquiry and factory visit!

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now