Vacuum Circuit Breaker, Circuit Breaker, Moulded Case Circuit Breaker manufacturer / supplier in China, offering Zw32-12 High Voltage Outdoor Vacuum Circuit Breaker with ISO9001-2000, Vs1/C-12 Vacuum Circuit Breaker with Lateral Operating Mechanism ISO9001-2000, Vib-40.5/T Indoor High Voltage Vacuum Circuit Breaker with Embedded Poles and so on.

(/ )

Supplier Homepage Product Outdoor HV Vacuum Circuit Breaker Zw32-12 High Voltage Outdoor Vacuum Circuit Breaker with ISO9001-2000

Zw32-12 High Voltage Outdoor Vacuum Circuit Breaker with ISO9001-2000

FOB Price: US $1,500-2,000 / Set
Min. Order: 1 Set
Min. Order FOB Price
1 Set US $1,500-2,000/ Set
Get Latest Price
Port: Shanghai, China
Production Capacity: 16000sets/Year
Payment Terms: L/C, T/T
Basic Info
  • Model NO.: ZW32-12
  • Operation: Electric Type
  • Arc-extinguishing Medium: Vacuum
  • Structure: MCCB
  • Type: Circuit Breaker
  • Certification: VDE, ISO9001-2000, CE, UL, CB, CCC
  • Rated Current: 630A
  • Trademark: Longxiang Electric
  • Specification: IEC: M2-E2-C2
  • HS Code: 85389000
  • Breaking Capacity: High Voltage Circuit Breakers
  • Speed: Normal Type Circuit Breaker
  • Installation: Fixed
  • Poles Number: 3
  • Function: Conventional Circuit Breaker
  • Rated Voltage: 12kv
  • Rated Frequency: 50/60Hz
  • Transport Package: Non-Solid Wooden Case for Export Shipment
  • Origin: China Baoji
Product Description


ZW32-12 Type Outdoor HV Vacuum Circuit Breaker

General Description
ZW32-12 type outdoor high voltage vacuum circuit breaker is three-phase AC,50(60) Hz outdoor power distribution equipment with the rated voltage of 12kV.It is mainly used to break and close the load current,and short circuit current in the electric power system.It fits to be used to protect and control the circuit in substation,mining and industrial enterprises.It also can be used in the frequently operation places such as the rural power network. The product is accordance with GB1984-2003 standard.
The ZW32-12G VCB -Isolating switch combination consists of Vacuum circuit breaker body and isolating switch.
Applying ambient conditions
1.Ambient temperature:-30ºC~+40ºC.
2.The height above sea level:≤1000m(besides the special requirements).
3.Relative humidity:the average humidity of a day should be no more than 95%;the average humidity of a month should be no more than 90%.
4.Saturated vapor pressure:the average pressure of a day should be no more than 2.2kPa:the  average pressure of a month should be no more than 1.8kPa.
5.Earthquake intensity:not exceed 8 degrees.
6.Wind pressure should be no more than 700pa(it is equivalent to wind sped of 34m/s).
7.The air filthy should be within III degree.
8.It should be installed in the places without fire,explosion,serious filth, chemical erosion and violent vibration.

Technical Data

 
S.NNameUnitData
1Rated voltagekV12
2Rated frequencyHz50/60
3Rated currentA630
4Rated short circuit breaking currentkA20
5Rated short circuit making currentkA50
6Rated peak withstand currentkA50
7Rated short time withstand currentkA20
8Rated short-circuit durationS4


 